Murco MGS Spezifikationen Seite 26

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 31
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 25
MGS Installation and Operation Manual
26 1000-0085 Rev 0
Figure 9. Gas Cylinder and Test Hardware
Gas ampoules are convenient and inexpensive alternatives to using gas
cylinders for bump testing.
Step Bump Testing Using Gas Ampoules
1
Make sure that both the ampoules and the calibration beaker are
clean and dry.
2
Unscrew the beaker hold screw and place the ampoule so that it
sits in the base of the beaker (see Figure 10).
3
Tighten the wing-nut screw onto
the ampoule without breaking it.
4
Remove the enclosure lid of the
gas detector.
5
Connect a voltmeter between pins
0V and VS to monitor sensor
response (in Volts DC).
Seitenansicht 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31

Kommentare zu diesen Handbüchern

Keine Kommentare