MGS Installation and Operation Manual
8 1000-0085 Rev 0
Section 2. Installation and Wiring
WARNING: Explosion hazard! Do not mount the MGS in an area
that may contain flammable liquids, vapors, or aerosols. Operation
of any electrical equipment in such an environment constitutes a
safety hazard.
CAUTION: The MGS contains sensitive electronic components
that can be easily damaged. Do not touch nor disturb any of these
components.
NOTE: The mounting location of the monitor should allow it to be
easily accessible for visual monitoring and servicing.
NOTE: The monitor must be connected by a marked, suitably
located and easily reached switch or circuit-breaker as means of
disconnection.
NOTE: Connect monitor power and signaling terminals using
wiring that complies with local electrical codes or regulations for the
intended application.
NOTE: This instrument can be equipped with a semiconductor
sensor for the detection of refrigerant, combustible and VOC gases.
Semiconductor sensors are not gas specific and respond to a variety
of other gases including propane exhaust, cleaners, and solvents.
Changes in temperature and humidity may also affect the sensor’s
performance.